SPECIFICATIONS FOR MODEL 2000C OPEN AND CLOSE
|
AUTOMATIC CONTROL FOR TON CYLINDER VALVES
|
|
|
OPERATION
The
Model 2000C is an actuator system to automatically open and close the
valve on chlorine or sulfur dioxide ton cylinders.
The system includes a battery operated actuator with electric
motor that rotates the valve stem toward open or closed position for alignment,
tests, and remote operation. The actuator is designed to mount without
interfering with or requiring yokes or additional adaptors for dispensers
or discharging hardware. The motor, gears, and controls are assembled
as one unit.
CAPABILITIES
- Battery operated with trickle charger
- Optional integral leak detection for automatic shutdown
- Remote control by leak detector, panic button, or other
digital signals such as PLC or computer
- Easy to install or remove
- Can be used on chlorine and sulfur dioxide containers
- Can be part of an automatic changeover system to permit
only one container in service at a time
- Eliminates the need for scrubbers in certain applications
per the Uniform Fire Code
FEATURES
The system includes a remote power supply enclosure for
trickle charge of the batteries. Placement of the actuator can be accomplished
by connection to the cylinder valve with an easy on/off latch. Monitor
and controls are accomplished through an on-board microprocessor with
integral LED displays for CLOSED, ALIGN, and OPEN. The LED display enables
the operator to easily read the condition when mounted outdoors with bright
sunlight. Programming is accomplished through an integral keypad. Valve
position is transmitted to the microprocessor from a direct-coupled potentiometer
and displayed in Degrees Open.
ADDITIONAL INFO
Inputs for remote control can include "open",
"close", and "latch close". Outputs for remote indication
can include "valve open", "valve closed", "leak",
or "fail".
For information on actuators that open and close 150-pound
cylinders refer to Specification Model U.
|
DETAILS
|
| Enclosure |
NEMA 4X |
| Battery |
18 V NimH or 12 V SLA |
| Trickle Charge |
120/240 VAC, .2 Amp |
| Indicator |
Three digit .5" LED |
| Inputs |
Maximum three |
| Outputs |
Maximum four |
| Remote |
Wired Power Enclosure |
Rotation
|
Programmable up to 360 degrees |
| Materials |
Fiberglass, stainless steel,
steel, brass, RF Nylon |
| Actuator wt. |
11 Pounds |
| Torque |
20 ft/pounds for test
40 ft/pounds for safety close |
| Compatibility |
Chlorine Institute 110 and Conforms
to CI Publication "RECOMMENDATIONS FOR EMERGENCY CLOSURE DEVICES
FOR CONTAINER VALVES" |
MODEL NUMBER ITEMS AND OPTIONS
|
| A |
B |
C |
D |
E |
F |
| Model 2000C |
- |
- |
- |
- |
- |
|
ITEM
|
OPTION
|
DESCRIPTION
|
A
STANDARDEQUIPMENT |
2000 |
Base price includes
actuator with hardware to mount on ton cylinder, manual open and close,
LED display for indication of closed, open, align, failed, and latched
closed. |
B
REMOTE POWER |
0 |
Integral power supply
and 4500 mAH battery pack, no remote power supply, weight increases
by 5 pounds. |
| X |
Specify number of actuators
required. One remote power supply enclosure to be furnished to accommodate
number of actuators. (Note 3 and Note 7) |
C
INPUTS |
0 |
Standard with terminals
for contact closure input, cable entry is CGB |
| 1 |
One, close receiver,
RF |
| 2 |
Three, RF (Note2 and
Note 5) |
| 3 |
Three, wired with quick
connect/disconnect (Note 2 and Note 6) |
D
OUTPUTS |
0 |
Standard with None |
| 4 |
Four, RF (Note 5) |
| 5 |
Four, wired with quick
connect/disconnect (Note 6) |
E
LEAK DETECTION |
0 |
None |
| 1 |
Integral leak detector
with automatic close (Specify chlorine or sulfur dioxide) |
F
REMOTE DEVICES |
0 |
None |
| 1 |
Remote Transmitter with
Panic Button (For one common input) |
| 2 |
Remote Control, RF,
with Panic Button |
| 3 |
Remote Terminal Box
with PB, HWT 008, (Note 3) Per eight actuators |
|
| *NOTE 1 |
The term "Latched Closed" represents
the action of the actuator after receiving a remote contact closure.
The actuator closes the valve and will not respond to other signals
until an acknowledgement is made on the actuator keypad. |
| *NOTE 2 |
Integral leak detector is required for
remote open option |
| *NOTE 3 |
Shielded cable furnished (30') and may
be connected to PLC/RTU without Terminal Box |
| *NOTE 4 |
Spares must be ordered separately and
may include: |
| |
Part # LD001 - Chlorine Sensor, 100 PPM |
| |
Part # LD003 - Sulfur dioxide Sensor,
100 PPM |
| |
Part # BA018 - 18/10 Volt, 4500 mAH,
NimH, battery pack |
|
Part # FS001 - Fuse (Package of 5) |
| *NOTE 5 |
When RF inputs and outputs are required,
select C=2 and D= 4. |
| *NOTE 6 |
When wired inputs and outputs are required,
select C= 3 and D=5. |
| *NOTE 7 |
The remote power supply enclosure includes
output relay for remote alarm signal, power and alarm lights. |
| |
|
|
|
|
|